BIGGEST
MISTAKES IN
INSTRUMENTATION
Mistake #1: Selecting
the wrong sensor
Technology
mismatch Although it’s generally obvious what quantity needs to be measured in
a flow, temperature, or pressure control application, it’s not always obvious
what kind of flow meter, temperature sensor, or pressure gauge is best suited
to the job. A mismatch between the sensing technology and the material to be
sensed can lead to skewed measurements and severely degraded control.
Mistake #2: Installing sensors incorrectly
The
best sensor can yield disappointing results if not installed correctly.
Mistake #3: Poor
Grounding
Instruments
must be grounded to provide a reference voltage for the data signals they
generate. Relying on earth ground is risky since not all of the earth shares
the same electrical potential. The resulting currents will interfere with the sensors’
signals.
While
it’s generally a good practice to insulate a sensor from the thermodynamic effects
of its surroundings it’s absolutely critical to establish electrical isolation.
The most common electrical problems due to poor installation are ground loops. Ground
loops occur when an extraneous current flows through the instrumentation wiring
between two points that are supposed to be at the same voltage, but aren’t (see
Figure ). The resulting electrical interference can cause random fluctuations
in the sensors’ output and may even damage the sensors themselves. As the name
implies, ground loops most often occur when instruments and their cables are
grounded improperly or not at all. Interestingly, the best way to isolate a
plant’s instruments from ground loop currents is to connect them together at
one master grounding point. If that’s not possible, a grid of grounding points
must be spread throughout the plant, making sure that all points on the grid
are at the same electrical potential. Insecure connections and inadequate wires
can cause a voltage imbalance in the grid and ground loops between the
instruments connected to it.
Mistake #4: Generating
gibberish
Noise
Ground
loops are not the only source of noise that can distort a sensor’s readings.
Radio frequency interference (RFI) is even more common in plants that use
walkie talkies, pagers, and wireless networks extensively. RFI also results whenever
a current changes, such as when an electro mechanical contact or a static
discharge generates a spark.
The
sources of RFI noise must be eliminated or at least kept away from the plant’s
instrumentation if at all possible. Replacing electro mechanical equipment with
solid state devices will eliminate arc-generated RFI.
Mistake #5: Quitting
to Soon
Calibration
Most
instrumentation engineers know that a sensor must be calibrated in order to
associate a numerical value with the electrical signal coming out of the
transmitter. Yet all too often, the instruments are calibrated just once during
installation then left to operate unattended for years. The result is an
insidious problem known as drift. A sensor’s output tends to creep higher and
higher (or lower and lower), even if the measured variable hasn’t changed.
Deposition
on the sensing surfaces, corrosion in the wiring, and long term wear on moving
parts can all cause an instrument to begin generating artificially high (or low)
readings. As a result, the controller will gradually increase or decrease its
control efforts to compensate for a non-existent error.
Planning for the road ahead
No comments:
Post a Comment