Saturday, 20 April 2013
Thursday, 18 April 2013
Glycol-Type Gas Dehydration Unit
A natural gas
stream can be dehydrated by contacting the gas with glycol. This process (see Figure
1) is normally carried out at an elevated pressure in a vessel called a
contactor or absorber. After absorbing the water, the glycol is reconcentrated
by boiling off the water at atmospheric pressure in a regenerator. A pump is
used to recirculate the glycol to the contactor.
Fig 1: Gas Dehydration Unit
Inlet Scrubber: An inlet scrubber is required, either
integral with the contactor or as a separate vessel upstream, to remove free
liquids from the gas stream going to the contactor. The mist extractor in this
vessel removes larger droplets entrained in the gas.
Contactor: The contactor vessels may be
categorized as to the manner in which the absorption process is accomplished.
One type uses trays equipped with bubble caps, valves, other devices, to maximize
gas-to glycol contact. The action of the gas flowing upward through the glycol
layer on each tray creates a froth above the tray, where most of the absorption
takes place. The other type of contactor is referred to as a packed tower. It
is filled with packing, which has a large surface area per unit volume. Glycol
flowing downward wets the entire packing surface. Absorption takes place as the
gas flows upward through the packing, contacting the wetted surface. In either
type of vessel, a mist extractor removes entrained glycol droplets from the
dehydrated gas stream before it leaves the top of the contactor. On larger units,
an optional residue gas scrubber may be justified. Rich (wet) glycol is
directed from the bottom of the contactor to the regeneration system.
Gas/Glycol Heat Exchanger: Absorption is
improved with lower temperature glycol. A gas/glycol heat exchanger is required
which uses dehydrated gas to cool the lean (dry) glycol before it enters the
top of the contactor.
Regeneration System: The
regeneration system consists of several pieces of equipment. If glycol-gas powered
pumps are installed, energy from the high pressure rich glycol along with a small
amount of gas is used to pump the lean glycol. If an optional reflux coil in
the still column is provided, the rich glycol flows through it before entering
the glycol/glycol heat exchanger. The glycol/glycol heat exchanger serves two purposes:
1) to cool the lean glycol to a temperature as recommended by the pump
manufacturer, and 2) to conserve energy by reducing the heat duty in the reboiler.
Gas-Condensate-Glycol Separator: A frequently used option in regeneration systems
is a gas-condensate glycol separator, and should be included when the inlet gas
contains condensate. It may be located upstream or downstream of the
glycol/glycol heat exchanger and usually operates at a pressure of 25-75 psig.
It removes condensate from the glycol prior to the reboiler, which minimizes
coking and foaming problems. The separator also captures flash gas that is
liberated from the glycol and exhaust gas from the glycol-gas powered pumps, so
that the gas may be used as fuel. Glycol is regulated from the separator to the
reboiler by means of a level controller and dump valve. Condensate removal may
be controlled automatically or manually.
Reboiler.:Rich glycol enters the reboiler through
the stili column. It is then heated to 350-400°F, which causes
the water that was absorbed in the contactor to vaporize. The reboiler is
usually heated by combustion of natural gas, but may utilize other fuels,
steam, hot oil or other heat sources. The regenerated lean glycol gravity feeds
from the reboiler, through the glycol/ glycol heat exchanger, and into the pump
suction for recirculation back to the contactor. Either electric, gas powered, or
glycol-gas powered pumps may be used.
Still Column: Water and glycol vapors from the reboiler
enter the bottom of the still column, which is mounted on top of the reboiler.
The bottom section contains packing, while the top section of the still
column may contain a reflux coil or external fins. Reboiier vapors are cooled
and partially condensed to provide reflux, which improves the separation
between glycol and water. The remaining water vapor leaves the top of the stili
column and vents into the atmosphere.
Filters and Strainers: Regeneration
systems contain various types of filters and strainers. A particle filter
or fine mesh strainer is required to protect the pump. To reduce foaming, an
activated carbon filter may be installed to remove heavy hydrocarbons from the
glycol.
Some important factors
to be considered on GDU Unit:
Firetube Heat Flux: The average
heat flux shall be no higher than 10,000 BTU/hr.-sq. It. of exposed area.
Example: 8%‘‘ O.D.
Sch. 20, 0.25” wall fire tube having 25.0 square feet of surface,
51.85 sq. in. cross sectional area and rated at 250,000 BTU/hr.
heat duty.
Average Heat Flux
= (Firetube Rating (BTU/hr))/ (Sq. Ft. of Firetube Surface) = 250000/25.0 =10,000
BTU/hr-sq. ft
Stack Height: The height of the stack shall be no less
than required to provide draft sufficient to overcome the pressure drop in the
firetube, flame arrestor, stack, returns. turbulators, dampeners, and stack flame
arrestor if provided. The operating site elevation shall be considered in the
draft calculations.
Process
Considerations:
Inlet Gas Temperature: One of the key
design and operating variables of a glycol-type gas dehydration unit is the
temperature of the entering wet gas. For operation, this temperature should be
maintained between 60°F and 120°F. At lower gas temperatures, glycol on the
contactor trays will become very viscous, resulting in reduced tray efficiency,
increased pressure drop, and glycol carryover. Higher Temperatures will increase
the amount of water vapor to be removed, as well as require very pure lean
glycol to meet the dehydration specification. Glycol vaporization losses will
also increase at higher gas temperatures.
Gas/Glycol Heat Exchanger: It is important
that the glycol entering the contactor be cooled to a 10°F to 30°F above
the temperature of the gas stream. This is necessary because the equilibrium
conditions between the glycol and the water vapor in the gas are affected by
temperature. At higher temperatures, more water vapor will remain in the gas
stream. A cooler glycol temperature will decrease the glycol vaporization
losses but hydrocarbons may condense in the contactor.
Glycol Reboiler Heat Flux/Temperature:Glycol degradation
should be minimized by designing the glycol reboiler firetube with an average
heat flux of no higher than 10,000 BTU/hr/ft2. The normal range of heat flux is
6,000 - 10,000 BTU/hr/ftZ. Burner flame pattern and flame length should also be
designed to avoid hot spots on the firetube. Bulk temperature for triethylene
glycol should not exceed 400°F. The maximum tube wail temperature should
not exceed 430°F
Circulation Rates: Typical glycol type gas
dehydration units have glycol circulation rates from 2.0 to 3.0 gallons
of glycol per pound of water removed- Varies depends on Unit Spec & gas
quality.
Glycol Losses: For a properly designed gas
dehydration unit during normal operation, the glycol losses should not exceed 0.1 gallon of glycol per
million standard cubic feet of gas dehydrated.
GDU- CORROSION
CONTROL:
Variables affecting Corrosion Potential: Stream
compositions, operating pressure and temperature conditions, and design/fabrication
details such as metallurgy, stress, welding procedures and heat treatment all
have a part in the corrosion potential of a system. Since carbon steel is the
major material of construction for typical glycol-type gas dehydration units,
corrosive environments require special considerations.
Stream Compositions.
Of primary concern is the presence of acid gases (carbon dioxide- CO, and/or
hydrogen sulfide-H,S) and/or oxygen-02 in the flow streams.
Carbon dioxide partial
pressures in the gas phase below 3 psia typically do not require corrosion
control. Between 3 and 30 psia, some form of corrosion control may be required,
such as pH control or inhibitor injection.
Corrosion resistant
metals may also be needed. For carbon dioxide (CO,) partial pressures above 30 psia,
design/operational corrosion control measures will be required. Hydrogen
sulfide (H2S) and oxygen (O2) are corrosive at very low concentrations. In
addition to corrosion, hydrogen sulfide (H,S) can lead to sulfide stress
cracking (SSC)
INSTALLATION,
START-UP, OPERATION AND MAINTENANCE
Installation:
All equipment must be installed on an adequate foundation. The equipment should
be as level as possible for the most efficient operation. All items shipped
loose should be installed on the unit. This may include the stack, still
column, piping between the regenerator and contactor, and the vent line from the
still column. Normally the still column vapors are vented directly to the
atmosphere.
Vent piping
should be kept to a minimum. It should be remembered that these vapors contain
combustible hydrocarbons, corrosive components, and water which may condense
and freeze. Therefore, consideration must be given to the location assembled, all screwed and bolted connections
should be checked for tightness.
Start-up:
The unit should
be inspected before start-up to make certain that all valves are closed and all
regulators are backed off.
All relief
valves and critical shutdown devices should be operational. Admit supply gas to
the system and open isolation valves under all pressure gauges.
The contactor
should be purged with natural gas to eliminate air. It then should be brought
up to line pressure and checked for leaks.
Maintain the
contactor pressure, but do not flow gas at this point. The flash tanks and piping
should also be purged to eliminate air.
Open the cocks
on the glycol surge tank level gauge and the valve in the line between the
surge tank and the glycol/glycol heat exchanger.
Fill the
reboiler with glycol until the level comes about half way up in the surge tank
gauge. Allow approximately 25% of the surge tank for thermal expansion of the
glycol.
The glycol
circulation, including the return to the reboiler from the contactor, should be
fully established prior to ignition of the main burner.
Light the pilot
light and main burner as recommended. Heat the glycol until it reaches 390°F
and set the temperature controller. Continue heating the glycol until it
reaches 400°F and set the high temperature shutdown. These temperatures are typical:
however, some manufacturers and operators prefer somewhat different
temperatures.
Operating conditions
can also sometimes require different operating temperatures. It is highly
recommended that the glycol never be heated above 400°F because it starts decomposing
at 405°F.
The glycol level
in the surge tank should be brought to normal after circulation has been
established. All gauge cocks should be open and level controls set at this time.
Gas flow may now
be started through the contactor. The flow rate should be increased slowly to
prevent losing
liquid seals and
damage to the trays.
The unit is now
ready for final adjustments. This includes checking the reboiler temperature
setting, circulation rate, burner adjustment, valve function, level controller
function, and glycol level in the sure tank.
It is very
important to make sure that steam is coming out of the vapor outlet of the
still column. The circulation rate should be in accordance with the process
design specification.
Operation:
Routine
operation of gas dehydration units primarily involves periodic visits to
determine if everything is operating properly.
As a minimum,
the following items should be checked:
a. inlet gas
temperature and flow rate
b. contactor
pressure
c. reboiler
temperature
d. pump
operation
e. steam
from still column
f. level
of glycol in surge tank
g. burner
flame pattern and firetube appearance.
It is necessary
to periodically add glycol to the surge tank because a certain amount of glycol
loss is normal.
Other than that,
the units are designed for unattended operation as long as everything is functioning
properly.
If the unit is
designed for manual dumping of distillate from the reboiler and/or the glycol
flash separator, it will be necessary to check these levels during the periodic
visits.
There are
numerous operating problems that can be encountered with these units. Some of
the most common will be
discussed here.
Two factors
which greatly affect the ability of a unit to dehydrate gas are gas pressure
and temperature.
Small changes
from design in these variables can have a large effect on the water content of
the gas. Gas flow rate has a somewhat
smaller effect on equipment performance.
Cold outside air
temperatures can render a unit inoperable. It can freeze instruments and
controls, and can cause hydrates to form in scrubbers. If a unit is located in
an area where this is a problem, precautions should be taken. Examples are
heating coils in scrubbers, heating jackets on liquid discharge lines, cold
weather shrouds on glycol/glycol heat exchangers, and housing the entire
regenerator
Proper operation
of a unit depends on the cleanliness of the gas being processed. Many times, it
is necessary to install a coalescing filter separator immediately ahead of the
unit. This will remove compressor lube oil fog, small solids, distillate, salt,
etc. These impurities can plug equipment, coat packing, render the glycol less effective,
and coat the firetube which will cause it to burn out.
Plugging in the
still column or vent line can cause pressure to build up in the reboiler and
surge tank. This pressure should be checked periodically. Caution should be
used when opening connections: for example, to add glycol.
There are ways
of removing distillate once it gets into the regeneration system. The surge
tank may have a skimmer valve on it by which the distillate can be manually
drained. If the glycol flash separator is designed as a three phase
vessel, distillate may also be removed from the system at this point.
Maintenance:
It is necessary
to check the pH of the glycol periodically. It should be a neutral solution. Values
that vary from neutral can lessen the ability of the glycol to absorb water,
and may cause foaming or corrosion.
The elements in
all filters (coalescing, charcoal, sock, regulators, etc.) need to be checked
periodically and replaced as necessary.
Pumps require
routine maintenance and overhauling.
Dehydration
units may become plugged and packing may get a coating buildup. When this
happens, it is necessary that the system be thoroughly cleaned.
Steam Trap-Steam Distribution Piping System
A steam trap is an essential element of a steam distribution piping system. As steam flows through a pipe, it cools off due to heat losses and converts into hot water; this hot water is called condensate. The function of a steam trap is to bleed off hot water so that only steam remains in the system. In addition to condensate removal, a steam trap also performs air venting function, thereby increasing the thermal efficiency and reliability of the steam distribution system.
A typical steam trap assembly consists of a number of components which enable the successful operation of the system.
1. Stop Valves: To control (stop or allow) the steam flow through the system.
2. Strainer: To remove debris from the steam; if debris is not removed, it might damage the trap.
3. Check Valve: It stops the condensate from flowing back to the system.
4. Trap: To catch water and allow the steam to flow through.
In normal practice, strainer and check valves are built in with the steam trap.
· Under normal operation, bypass stop valve remains closed and the other two stop valves remain open. Steam flows through the trap, where condensate is removed and drained while the steam returns to the steam mains. In some plants, condensate is recovered and returned to the boiler feed water tank. This results in significant savings in terms of energy and water usage.
Wednesday, 17 April 2013
Measuring Hydrocarbon Dew Point of Natural Gas Fuel for Gas Turbine
Natural
gas is used by a number of industries, most notably in power generation by gas
turbines.
Gas
turbine manufacturers will always provide specifications defining the quality
of the natural gas fuel provided
to the turbine - designed to prevent damage to the turbine and the additional
problems that can result. These specifications can include a number of parameters,
including pressure, flow, acceptable contaminant limits and gas temperature –
frequently with the inclusion of the term ‘superheat’.
When
operating modern DLN (Dry low NOx) turbines, the following of these guidelines
is critical to avoiding severe damage to the turbine, and criteria such as
superheat have been set up to help prevent this. Superheat is defined as the
temperature 50°F (28°C) above the Hydrocarbon and water Dew Points of the fuel
gas, so if the dew point of the gas is -12°C, then the gas should be heated to
+10°C.
Prior
to combustion, the gas is running at pipeline pressure, much too great for the
gas turbine, therefore the gas must be expanded in order to be suitable for
use. As the pressure of the gas drops, so does the temperature. If this Joule- Thompson
effect drops the temperature below the HCDP, then liquids will condense inside
the burner tubes of the turbine and the cans and nozzles coke up and become
significantly less efficient, causing dramatically increased NOx emissions. If
this situation is allowed to continue for a short time, the burner section will
need to be rebuilt. This means a 3-5 day unplanned shut-down, a large crew
on-site around the clock for the expensive rebuild and lost revenue and plant
availability. This will dramatically impact the profitability of the plant.
Another
seriously costly effect of condensation is flashback. This can be caused by
hydrocarbon condensates, and the effect is for a flame to be held downstream of
the burners, in the recirculation area. This region is not designed to withstand
heat of this nature, and the metal temperatures will increase dramatically,
frequently causing physical damage to the hardware.
Superheat
is designed to help prevent either of these occurrences by ensuring that the
gas never comes close to its HCDP. Natural gas fuel conditioning systems are
most commonly used to heat the incoming gas, but this heat requires energy to
generate, and if overheating due to a lack of awareness of the gas dew point occurs,
then large costs can be incurred.
Measurement Techniques:
There
are a number of different accepted methods for measuring HCDP,
1) The
original technique being to use a cooled mirror dewscope. This requires a
skilled operator to view a mirror over which the sample is flowed. The mirror
is then cooled, and the temperature at which the first drops of condensation
are viewed is noted.
2) Another
method of determining the HCDP is by means of a gas chromatograph (GC). This
method determines the concentrations of each hydrocarbon element (up to C12 in
most cases), and, through an equation of state calculation, the condensing
points of the quantities of each component present are identified and calculated
to give a hydrocarbon dew point for the complete mixture. However, due to the
limitations of the device, when analysing heavy hydrocarbon molecules the
calculations of the HCDP can frequently be quite inaccurate, suggesting that
the HCDP is drier than the actual value.
3) The
alternative is to use an automatic, optical condensation dew-point analyser, such
as the Michell Instruments Condumax II, Ametek. These devices functions in a
similar manner to the Cooled mirror dewscope. The cell has an etched optical
surface with a central conical depression which normally refracts light
unevenly. An LED shines at this surface and a photo-detector looks at an image
of the light shining back, which in dry conditions, appears as a ring of light.
The photo-detector is focused on the light scattered into the centre of the
ring. A thermoelectric peltier device cools the surface until condensates begin
to appear. The condensates alter the reflective properties of the surface, with
the circle of light around the perimeter intensifying, and the scattered light
in the centre dispersing according to the amount of condensate on the mirror.
The exact signal level can be accurately monitored by looking at the signal
from the photodetector. The mirror temperature is recorded when the desired
level of condensates are deposited. The setting of the device gives readings
which are comparable to readings obtained by an experienced dewscope operator.
Centrifugal Pumps: Understanding Cavitation
Centrifugal Pumps: Understanding Cavitation
Operating a pump under the condition of cavitation for even
a short period of time can have damaging consequences for both the equipment
and the process.
Continuous operation
of centrifugal pumps at low flows i.e. reduced capacities, leads to a number of
unfavorable conditions. These include reduced motor efficiency, excessive
radial thrusts, excessive temperature rise in the pumping fluid, internal
re-circulation, etc. A certain minimum continuous flow (MCF) should be
maintained during the pump operation.
The condition of cavitation is essentially an indication of
an abnormality in the pump suction system.
Cavitation is a common occurrence but is the least
understood of all pumping problems. Cavitation means different things to
different people. Some say when a pump makes a rattling or knocking sound along
with vibrations, it is cavitating. Some call it slippage as the pump discharge
pressure slips and flow becomes erratic. When cavitating, the pump not only
fails to serve its basic purpose of pumping the liquid but also may experience
internal damage, leakage from the seal and casing, bearing failure, etc.
In the context of centrifugal pumps, the term cavitation
implies a dynamic process of formation of bubbles inside the liquid, their
growth and subsequent collapse as the liquid flows through the pump.
Generally, the bubbles that form inside the liquid are of
two types: Vapor bubbles or Gas bubbles.
Vapor bubbles are formed due to the vaporization of a
process liquid that is being pumped. The cavitation condition induced by
formation and collapse of vapor bubbles - Vaporous Cavitation.
Gas bubbles are formed due to the presence of dissolved
gases in the liquid that is being pumped (generally air but may be any gas in
the system)-Gaseous Cavitation.
Both types of bubbles are formed at a point inside the pump
where the local static pressure is less than the vapor pressure of the liquid
(vaporous cavitation) or saturation pressure of the gas (gaseous cavitation).
Vaporous cavitation is the most common form of cavitation
found in process plants. Generally it occurs due to insufficiency of the
available NPSH or internal recirculation phenomenon. It generally manifests
itself in the form of reduced pump performance, excessive noise and vibrations
and wear of pump parts.
Gaseous cavitation occurs when any gas (most commonly air)
enters a centrifugal pump along with liquid. A centrifugal pump can handle air
in the range of ½ % by volume. If the amount of air is increased to 6%, the
pump starts cavitating.
Mechanism of Cavitation :
The phenomenon of cavitation is a stepwise process as shown
in Figure
The bubbles form inside the liquid when it vaporises i.e.
phase change from liquid to vapor. But how does vaporization of the liquid
occur during a pumping operation?
Vaporization of any liquid inside a closed container can
occur if either pressure on the liquid surface decreases such that it becomes
equal to or less than the liquid vapor pressure at the operating temperature,
or the temperature of the liquid rises, raising the vapor pressure such that it
becomes equal to or greater than the operating pressure at the liquid surface.
For example, if water at room temperature (about 77 °F) is kept in a closed
container and the system pressure is reduced to its vapor pressure (about 0.52
psia), the water quickly changes to a vapor. Also, if the operating pressure is
to remain constant at about 0.52 psia and the temperature is allowed to rise
above 77 °F, then the water quickly changes to a vapor.
Just like in a closed container, vaporization of the liquid
can occur in centrifugal pumps when the local static pressure reduces below
that of the vapor pressure of the liquid at the pumping temperature.
Valve Sizing and Selection
Valve
Sizing and Selection
a. Never use a valve that is less than half the
pipe size
b. Avoid using the lower 10% and upper 20% of the valve stroke. The valve is much easier to control in the 10-80% stroke range.
Before a valve can be selected, you have to decide what type of valve will be used (See the list of valve types later in this article). For our case, we'll assume we're using an equal percentage, globe valve (equal percentage will be explained later). The valve chart for this type of valve is shown below. This is a typical chart that will be supplied by the manufacturer (as a matter of fact, it was)
So we've selected a valve...but are we ready to order? Not yet, there are still some characteristics to consider.
Gain is defined as:
we have corresponding Cv values of 6.5, 28, and 39. The corresponding stroke percentages are 35%, 73%, and 85% respectively. Now we construct the following table:
Gain #1 = 85/38 = 2.2
Gain #2 = 40/12 = 3.3
Another valve characteristic that can be examined is called the choked flow. The relation uses the FL value found on the valve chart. I recommend checking the choked flow for vastly different maximum and minimum flowrates. For example if the difference between the maximum and minimum flows is above 90% of the maximum flow, you may want to check the choked flow. Usually, the rule of thumb for determining the maximum pressure drop across the valve also helps to avoid choking flow.
1. Equal Percentage: equal increments of valve travel produce an equal percentage in flow change
2. Linear: valve travel is directly proportional to the valve stoke
3. Quick opening: large increase in flow with a small change in valve stroke
So how do you decide which valve control to use? Here are some rules of thumb for each one:
Now
that we've covered the various types of valve control, we'll take a look at the
most common valve types.
Butterfly
Valves:
Sizing flow valves is a science with many rules
of thumb that few people agree on. In this article I'll try to define a more
standard procedure for sizing a valve as well as helping to select the
appropriate type of valve. **Please note that the correlation within this
article is for turbulent flow.
Step #1: Define the System
The system is pumping water from one tank to
another through a piping system with a total pressure drop of 150 psi. The
fluid is water at 70 °F. Design (maximum) flowrate of 150 gpm, operating
flowrate of 110 gpm, and a minimum flowrate of 25 gpm. The pipe diameter is 3
inches. At 70 °F, water has a specific gravity of 1.0.
Key Variables: Total pressure drop, design
flow, operating flow, minimum flow, pipe diameter, specific gravity
Step #2: Define a maximum allowable pressure
drop for the valve
When defining the allowable pressure drop
across the valve, you should first investigate the pump. What is its maximum available head? Remember
that the system pressure drop is limited by the pump. Essentially the Net
Positive Suction Head Available (NPSHA) minus the Net Positive Suction Head
Required (NPSHR) is the maximum available pressure drop for the valve to use
and this must not be exceeded or another pump will be needed. It's important to
remember the trade off, larger pressure drops increase the pumping cost
(operating) and smaller pressure drops increase the valve cost because a larger
valve is required (capital cost). The usual rule of thumb is that a valve
should be designed to use 10-15% of the total pressure drop or 10 psi,
whichever is greater. For our system, 10% of the total pressure drop is 15 psi
which is what we'll use as our allowable pressure drop when the valve is wide
open (the pump is our system is easily capable of the additional pressure
drop).
Step
#3: Calculate the valve characteristic
For our system:
At
this point, some people would be tempted to go to the valve charts or
characteristic curves and select a valve. Don't make this mistake, instead,
proceed to Step #4!
Step #4: Preliminary valve selection
Don't make the
mistake of trying to match a valve with your calculated Cv value. The Cv value
should be used as a guide in the valve selection, not a hard and fast rule.
Some other considerations are:
b. Avoid using the lower 10% and upper 20% of the valve stroke. The valve is much easier to control in the 10-80% stroke range.
Before a valve can be selected, you have to decide what type of valve will be used (See the list of valve types later in this article). For our case, we'll assume we're using an equal percentage, globe valve (equal percentage will be explained later). The valve chart for this type of valve is shown below. This is a typical chart that will be supplied by the manufacturer (as a matter of fact, it was)
For
our case, it appears the 2 inch valve will work well for our Cv value at about
80-85% of the stroke range. Notice that we're not trying to squeeze our Cv into
the 1 1/2 valve which would need to be at 100% stroke to handle our maximum
flow. If this valve were used, two consequences would be experienced: the
pressure drop would be a little higher than 15 psi at our design (max) flow and
the valve would be difficult to control at maximum flow. Also, there would be
no room for error with this valve, but the valve we've chosen will allow for
flow surges beyond the 150 gpm range with severe headaches!
So we've selected a valve...but are we ready to order? Not yet, there are still some characteristics to consider.
Step
#5: Check the Cv and stroke percentage at the minimum flow
If the stroke percentage falls below 10% at our
minimum flow, a smaller valve may have to be used in some cases. Judgments plays role in many cases. For example, is your system more likely to operate
closer to the maximum flow rates more often than the minimum flow rates Or is it
more likely to operate near the minimum flow rate for extended periods of time.
It's difficult to find the perfect valve, but you should find one that operates
well most of the time. Let's check the valve we've selected for our system:
Referring
back to our valve chart, we see that a Cv of 6.5 would correspond to a stroke
percentage of around 35-40% which is certainly acceptable. Notice that we used
the maximum pressure drop of 15 psi once again in our calculation. Although the
pressure drop across the valve will be lower at smaller flow rates using the
maximum value gives us a "worst case" scenario. If our Cv at the
minimum flow would have been around 1.5, there would not really be a problem
because the valve has a Cv of 1.66 at 10% stroke and since we use the maximum
pressure drop, our estimate is conservative. Essentially, at lower pressure
drops, Cv would only increase which in this case would be advantageous.
Step
#6: Check the gain across applicable flow rates
Gain is defined as:
Now, at our three
flowrates:
Qmin = 25 gpm
Qop = 110 gpm
Qdes = 150 gpm
Qmin = 25 gpm
Qop = 110 gpm
Qdes = 150 gpm
we have corresponding Cv values of 6.5, 28, and 39. The corresponding stroke percentages are 35%, 73%, and 85% respectively. Now we construct the following table:
Flow (gpm)
|
Stroke (%)
|
Change in flow
(gpm)
|
Change in Stroke
(%)
|
25
|
35
|
110-25 = 85
|
73-35 = 38
|
110
|
73
|
||
150
|
85
|
150-110 = 40
|
85-73 = 12
|
Gain #1 = 85/38 = 2.2
Gain #2 = 40/12 = 3.3
The difference between these values should be
less than 50% of the higher value. 0.5
(3.3) = 1.65 and 3.3 - 2.2 = 1.10. Since 1.10 is less than 1.65, there should
be no problem in controlling the valve. Also note that the gain should never be
less than 0.50. So for our case, I believe our selected valve will do nicely!
Other
Notes
Another valve characteristic that can be examined is called the choked flow. The relation uses the FL value found on the valve chart. I recommend checking the choked flow for vastly different maximum and minimum flowrates. For example if the difference between the maximum and minimum flows is above 90% of the maximum flow, you may want to check the choked flow. Usually, the rule of thumb for determining the maximum pressure drop across the valve also helps to avoid choking flow.
Selecting a Valve Type
When speaking of valves, it's easy to get lost
in the terminology. Valve types are used to describe the mechanical
characteristics and geometry (Ex/ gate, ball, globe valves). We'll use valve
control to refer to how the valve travel or stroke (openness) relates to the
flow:
1. Equal Percentage: equal increments of valve travel produce an equal percentage in flow change
2. Linear: valve travel is directly proportional to the valve stoke
3. Quick opening: large increase in flow with a small change in valve stroke
So how do you decide which valve control to use? Here are some rules of thumb for each one:
1. Equal Percentage (most commonly
used valve control)
a. Used in processes where large
changes in pressure drop are expected
b. Used in processes where a small
percentage of the total pressure drop is permitted by the valve
c. Used in temperature and pressure
control loops
2. Linear
a. Used in liquid level or flow loops
b. Used in systems where the pressure
drop across the valve is expected to remain fairly constant (ie. steady state
systems)
3. Quick Opening
a. Used for frequent on-off service
b. Used for processes where
"instantly" large flow is needed (ie. safety systems or cooling water
systems)
Gate Valves:
Best Suited Control:
Quick Opening
Recommended Uses:
1. Fully
open/closed, non-throttling 2. Infrequent operation 3. Minimal fluid trapping
in line
Applications: Oil,
gas, air, slurries, heavy liquids, steam, noncondensing gases, and corrosive
liquids
Advantages:
1. High capacity ,
2. Tight shutoff 3. Low cost 4. Little resistance to flow
Disadvantages:
1. Poor control, 2.
Cavitate at low pressure drops, 3. Cannot be used for throttling
Globe Valves
Best Suited Control: Linear and Equal
percentage
Recommended Uses:
1. Throttling service/flow regulation
2. Frequent operation
Applications: Liquids, vapors, gases,
corrosive substances, slurries
Advantages:
1. Efficient throttling 2. Accurate flow control 3. Available in multiple ports
Disadvantages:
1.High
pressure drop 2. More expensive than other valves
Ball Valves:
Best Suited Control: Quick opening, linear
Recommended Uses:
1. Fully open/closed, limited-throttling 2. Higher temperature
fluids
Applications: Most liquids, high temperatures, slurries
Advantages:
1. Low cost 2. High
capacity 3. Low leakage and maint. 4.
Tight sealing with low torque
Disadvantages:
1. Poor throttling characteristics 2. Prone to cavitation
Best Suited
Control: Linear, Equal percentage
Recommended Uses:
1. Fully
open/closed or throttling services 2. Frequent operation 3. Minimal fluid
trapping in line
Applications:
Liquids, gases, slurries, liquids with suspended solids
Advantages:
1. Low cost and
maint. 2. High capacity 3. Good flow control 4. Low pressure drop
Disadvantages:
1. High torque
required for control 2. Prone to cavitation at lower flows
Other Valves
Another type of
valve commonly used in conjunction with other valves is called a check valve.
Check valves are designed to restrict the flow to one direction. If the flow
reverses direction, the check valve closes. Relief valves are used to regulate
the operating pressure of incompressible flow. Safety valves are used to
release excess pressure in gases or compressible fluids.
References
Rosaler, Robert C.,
Standard Handbook of Plant Engineering, McGraw-Hill, New York, 1995, pages
10-110 through 10-122
Purcell, Michael
K., "Easily Select and Size Control Valves", Chemical Engineering
Progress, March 1999, pages 45-50
Subscribe to:
Posts (Atom)