Valve
Sizing and Selection
a. Never use a valve that is less than half the
pipe size
b. Avoid using the lower 10% and upper 20% of the valve stroke. The valve is much easier to control in the 10-80% stroke range.
Before a valve can be selected, you have to decide what type of valve will be used (See the list of valve types later in this article). For our case, we'll assume we're using an equal percentage, globe valve (equal percentage will be explained later). The valve chart for this type of valve is shown below. This is a typical chart that will be supplied by the manufacturer (as a matter of fact, it was)
So we've selected a valve...but are we ready to order? Not yet, there are still some characteristics to consider.
Gain is defined as:
we have corresponding Cv values of 6.5, 28, and 39. The corresponding stroke percentages are 35%, 73%, and 85% respectively. Now we construct the following table:
Gain #1 = 85/38 = 2.2
Gain #2 = 40/12 = 3.3
Another valve characteristic that can be examined is called the choked flow. The relation uses the FL value found on the valve chart. I recommend checking the choked flow for vastly different maximum and minimum flowrates. For example if the difference between the maximum and minimum flows is above 90% of the maximum flow, you may want to check the choked flow. Usually, the rule of thumb for determining the maximum pressure drop across the valve also helps to avoid choking flow.
1. Equal Percentage: equal increments of valve travel produce an equal percentage in flow change
2. Linear: valve travel is directly proportional to the valve stoke
3. Quick opening: large increase in flow with a small change in valve stroke
So how do you decide which valve control to use? Here are some rules of thumb for each one:
Now
that we've covered the various types of valve control, we'll take a look at the
most common valve types.
Butterfly
Valves:
Sizing flow valves is a science with many rules
of thumb that few people agree on. In this article I'll try to define a more
standard procedure for sizing a valve as well as helping to select the
appropriate type of valve. **Please note that the correlation within this
article is for turbulent flow.
Step #1: Define the System
The system is pumping water from one tank to
another through a piping system with a total pressure drop of 150 psi. The
fluid is water at 70 °F. Design (maximum) flowrate of 150 gpm, operating
flowrate of 110 gpm, and a minimum flowrate of 25 gpm. The pipe diameter is 3
inches. At 70 °F, water has a specific gravity of 1.0.
Key Variables: Total pressure drop, design
flow, operating flow, minimum flow, pipe diameter, specific gravity
Step #2: Define a maximum allowable pressure
drop for the valve
When defining the allowable pressure drop
across the valve, you should first investigate the pump. What is its maximum available head? Remember
that the system pressure drop is limited by the pump. Essentially the Net
Positive Suction Head Available (NPSHA) minus the Net Positive Suction Head
Required (NPSHR) is the maximum available pressure drop for the valve to use
and this must not be exceeded or another pump will be needed. It's important to
remember the trade off, larger pressure drops increase the pumping cost
(operating) and smaller pressure drops increase the valve cost because a larger
valve is required (capital cost). The usual rule of thumb is that a valve
should be designed to use 10-15% of the total pressure drop or 10 psi,
whichever is greater. For our system, 10% of the total pressure drop is 15 psi
which is what we'll use as our allowable pressure drop when the valve is wide
open (the pump is our system is easily capable of the additional pressure
drop).
Step
#3: Calculate the valve characteristic
For our system:
At
this point, some people would be tempted to go to the valve charts or
characteristic curves and select a valve. Don't make this mistake, instead,
proceed to Step #4!
Step #4: Preliminary valve selection
Don't make the
mistake of trying to match a valve with your calculated Cv value. The Cv value
should be used as a guide in the valve selection, not a hard and fast rule.
Some other considerations are:
b. Avoid using the lower 10% and upper 20% of the valve stroke. The valve is much easier to control in the 10-80% stroke range.
Before a valve can be selected, you have to decide what type of valve will be used (See the list of valve types later in this article). For our case, we'll assume we're using an equal percentage, globe valve (equal percentage will be explained later). The valve chart for this type of valve is shown below. This is a typical chart that will be supplied by the manufacturer (as a matter of fact, it was)
For
our case, it appears the 2 inch valve will work well for our Cv value at about
80-85% of the stroke range. Notice that we're not trying to squeeze our Cv into
the 1 1/2 valve which would need to be at 100% stroke to handle our maximum
flow. If this valve were used, two consequences would be experienced: the
pressure drop would be a little higher than 15 psi at our design (max) flow and
the valve would be difficult to control at maximum flow. Also, there would be
no room for error with this valve, but the valve we've chosen will allow for
flow surges beyond the 150 gpm range with severe headaches!
So we've selected a valve...but are we ready to order? Not yet, there are still some characteristics to consider.
Step
#5: Check the Cv and stroke percentage at the minimum flow
If the stroke percentage falls below 10% at our
minimum flow, a smaller valve may have to be used in some cases. Judgments plays role in many cases. For example, is your system more likely to operate
closer to the maximum flow rates more often than the minimum flow rates Or is it
more likely to operate near the minimum flow rate for extended periods of time.
It's difficult to find the perfect valve, but you should find one that operates
well most of the time. Let's check the valve we've selected for our system:
Referring
back to our valve chart, we see that a Cv of 6.5 would correspond to a stroke
percentage of around 35-40% which is certainly acceptable. Notice that we used
the maximum pressure drop of 15 psi once again in our calculation. Although the
pressure drop across the valve will be lower at smaller flow rates using the
maximum value gives us a "worst case" scenario. If our Cv at the
minimum flow would have been around 1.5, there would not really be a problem
because the valve has a Cv of 1.66 at 10% stroke and since we use the maximum
pressure drop, our estimate is conservative. Essentially, at lower pressure
drops, Cv would only increase which in this case would be advantageous.
Step
#6: Check the gain across applicable flow rates
Gain is defined as:
Now, at our three
flowrates:
Qmin = 25 gpm
Qop = 110 gpm
Qdes = 150 gpm
Qmin = 25 gpm
Qop = 110 gpm
Qdes = 150 gpm
we have corresponding Cv values of 6.5, 28, and 39. The corresponding stroke percentages are 35%, 73%, and 85% respectively. Now we construct the following table:
Flow (gpm)
|
Stroke (%)
|
Change in flow
(gpm)
|
Change in Stroke
(%)
|
25
|
35
|
110-25 = 85
|
73-35 = 38
|
110
|
73
|
||
150
|
85
|
150-110 = 40
|
85-73 = 12
|
Gain #1 = 85/38 = 2.2
Gain #2 = 40/12 = 3.3
The difference between these values should be
less than 50% of the higher value. 0.5
(3.3) = 1.65 and 3.3 - 2.2 = 1.10. Since 1.10 is less than 1.65, there should
be no problem in controlling the valve. Also note that the gain should never be
less than 0.50. So for our case, I believe our selected valve will do nicely!
Other
Notes
Another valve characteristic that can be examined is called the choked flow. The relation uses the FL value found on the valve chart. I recommend checking the choked flow for vastly different maximum and minimum flowrates. For example if the difference between the maximum and minimum flows is above 90% of the maximum flow, you may want to check the choked flow. Usually, the rule of thumb for determining the maximum pressure drop across the valve also helps to avoid choking flow.
Selecting a Valve Type
When speaking of valves, it's easy to get lost
in the terminology. Valve types are used to describe the mechanical
characteristics and geometry (Ex/ gate, ball, globe valves). We'll use valve
control to refer to how the valve travel or stroke (openness) relates to the
flow:
1. Equal Percentage: equal increments of valve travel produce an equal percentage in flow change
2. Linear: valve travel is directly proportional to the valve stoke
3. Quick opening: large increase in flow with a small change in valve stroke
So how do you decide which valve control to use? Here are some rules of thumb for each one:
1. Equal Percentage (most commonly
used valve control)
a. Used in processes where large
changes in pressure drop are expected
b. Used in processes where a small
percentage of the total pressure drop is permitted by the valve
c. Used in temperature and pressure
control loops
2. Linear
a. Used in liquid level or flow loops
b. Used in systems where the pressure
drop across the valve is expected to remain fairly constant (ie. steady state
systems)
3. Quick Opening
a. Used for frequent on-off service
b. Used for processes where
"instantly" large flow is needed (ie. safety systems or cooling water
systems)
Gate Valves:
Best Suited Control:
Quick Opening
Recommended Uses:
1. Fully
open/closed, non-throttling 2. Infrequent operation 3. Minimal fluid trapping
in line
Applications: Oil,
gas, air, slurries, heavy liquids, steam, noncondensing gases, and corrosive
liquids
Advantages:
1. High capacity ,
2. Tight shutoff 3. Low cost 4. Little resistance to flow
Disadvantages:
1. Poor control, 2.
Cavitate at low pressure drops, 3. Cannot be used for throttling
Globe Valves
Best Suited Control: Linear and Equal
percentage
Recommended Uses:
1. Throttling service/flow regulation
2. Frequent operation
Applications: Liquids, vapors, gases,
corrosive substances, slurries
Advantages:
1. Efficient throttling 2. Accurate flow control 3. Available in multiple ports
Disadvantages:
1.High
pressure drop 2. More expensive than other valves
Ball Valves:
Best Suited Control: Quick opening, linear
Recommended Uses:
1. Fully open/closed, limited-throttling 2. Higher temperature
fluids
Applications: Most liquids, high temperatures, slurries
Advantages:
1. Low cost 2. High
capacity 3. Low leakage and maint. 4.
Tight sealing with low torque
Disadvantages:
1. Poor throttling characteristics 2. Prone to cavitation
Best Suited
Control: Linear, Equal percentage
Recommended Uses:
1. Fully
open/closed or throttling services 2. Frequent operation 3. Minimal fluid
trapping in line
Applications:
Liquids, gases, slurries, liquids with suspended solids
Advantages:
1. Low cost and
maint. 2. High capacity 3. Good flow control 4. Low pressure drop
Disadvantages:
1. High torque
required for control 2. Prone to cavitation at lower flows
Other Valves
Another type of
valve commonly used in conjunction with other valves is called a check valve.
Check valves are designed to restrict the flow to one direction. If the flow
reverses direction, the check valve closes. Relief valves are used to regulate
the operating pressure of incompressible flow. Safety valves are used to
release excess pressure in gases or compressible fluids.
References
Rosaler, Robert C.,
Standard Handbook of Plant Engineering, McGraw-Hill, New York, 1995, pages
10-110 through 10-122
Purcell, Michael
K., "Easily Select and Size Control Valves", Chemical Engineering
Progress, March 1999, pages 45-50
No comments:
Post a Comment