A natural gas
stream can be dehydrated by contacting the gas with glycol. This process (see Figure
1) is normally carried out at an elevated pressure in a vessel called a
contactor or absorber. After absorbing the water, the glycol is reconcentrated
by boiling off the water at atmospheric pressure in a regenerator. A pump is
used to recirculate the glycol to the contactor.
Fig 1: Gas Dehydration Unit
Inlet Scrubber: An inlet scrubber is required, either
integral with the contactor or as a separate vessel upstream, to remove free
liquids from the gas stream going to the contactor. The mist extractor in this
vessel removes larger droplets entrained in the gas.
Contactor: The contactor vessels may be
categorized as to the manner in which the absorption process is accomplished.
One type uses trays equipped with bubble caps, valves, other devices, to maximize
gas-to glycol contact. The action of the gas flowing upward through the glycol
layer on each tray creates a froth above the tray, where most of the absorption
takes place. The other type of contactor is referred to as a packed tower. It
is filled with packing, which has a large surface area per unit volume. Glycol
flowing downward wets the entire packing surface. Absorption takes place as the
gas flows upward through the packing, contacting the wetted surface. In either
type of vessel, a mist extractor removes entrained glycol droplets from the
dehydrated gas stream before it leaves the top of the contactor. On larger units,
an optional residue gas scrubber may be justified. Rich (wet) glycol is
directed from the bottom of the contactor to the regeneration system.
Gas/Glycol Heat Exchanger: Absorption is
improved with lower temperature glycol. A gas/glycol heat exchanger is required
which uses dehydrated gas to cool the lean (dry) glycol before it enters the
top of the contactor.
Regeneration System: The
regeneration system consists of several pieces of equipment. If glycol-gas powered
pumps are installed, energy from the high pressure rich glycol along with a small
amount of gas is used to pump the lean glycol. If an optional reflux coil in
the still column is provided, the rich glycol flows through it before entering
the glycol/glycol heat exchanger. The glycol/glycol heat exchanger serves two purposes:
1) to cool the lean glycol to a temperature as recommended by the pump
manufacturer, and 2) to conserve energy by reducing the heat duty in the reboiler.
Gas-Condensate-Glycol Separator: A frequently used option in regeneration systems
is a gas-condensate glycol separator, and should be included when the inlet gas
contains condensate. It may be located upstream or downstream of the
glycol/glycol heat exchanger and usually operates at a pressure of 25-75 psig.
It removes condensate from the glycol prior to the reboiler, which minimizes
coking and foaming problems. The separator also captures flash gas that is
liberated from the glycol and exhaust gas from the glycol-gas powered pumps, so
that the gas may be used as fuel. Glycol is regulated from the separator to the
reboiler by means of a level controller and dump valve. Condensate removal may
be controlled automatically or manually.
Reboiler.:Rich glycol enters the reboiler through
the stili column. It is then heated to 350-400°F, which causes
the water that was absorbed in the contactor to vaporize. The reboiler is
usually heated by combustion of natural gas, but may utilize other fuels,
steam, hot oil or other heat sources. The regenerated lean glycol gravity feeds
from the reboiler, through the glycol/ glycol heat exchanger, and into the pump
suction for recirculation back to the contactor. Either electric, gas powered, or
glycol-gas powered pumps may be used.
Still Column: Water and glycol vapors from the reboiler
enter the bottom of the still column, which is mounted on top of the reboiler.
The bottom section contains packing, while the top section of the still
column may contain a reflux coil or external fins. Reboiier vapors are cooled
and partially condensed to provide reflux, which improves the separation
between glycol and water. The remaining water vapor leaves the top of the stili
column and vents into the atmosphere.
Filters and Strainers: Regeneration
systems contain various types of filters and strainers. A particle filter
or fine mesh strainer is required to protect the pump. To reduce foaming, an
activated carbon filter may be installed to remove heavy hydrocarbons from the
glycol.
Some important factors
to be considered on GDU Unit:
Firetube Heat Flux: The average
heat flux shall be no higher than 10,000 BTU/hr.-sq. It. of exposed area.
Example: 8%‘‘ O.D.
Sch. 20, 0.25” wall fire tube having 25.0 square feet of surface,
51.85 sq. in. cross sectional area and rated at 250,000 BTU/hr.
heat duty.
Average Heat Flux
= (Firetube Rating (BTU/hr))/ (Sq. Ft. of Firetube Surface) = 250000/25.0 =10,000
BTU/hr-sq. ft
Stack Height: The height of the stack shall be no less
than required to provide draft sufficient to overcome the pressure drop in the
firetube, flame arrestor, stack, returns. turbulators, dampeners, and stack flame
arrestor if provided. The operating site elevation shall be considered in the
draft calculations.
Process
Considerations:
Inlet Gas Temperature: One of the key
design and operating variables of a glycol-type gas dehydration unit is the
temperature of the entering wet gas. For operation, this temperature should be
maintained between 60°F and 120°F. At lower gas temperatures, glycol on the
contactor trays will become very viscous, resulting in reduced tray efficiency,
increased pressure drop, and glycol carryover. Higher Temperatures will increase
the amount of water vapor to be removed, as well as require very pure lean
glycol to meet the dehydration specification. Glycol vaporization losses will
also increase at higher gas temperatures.
Gas/Glycol Heat Exchanger: It is important
that the glycol entering the contactor be cooled to a 10°F to 30°F above
the temperature of the gas stream. This is necessary because the equilibrium
conditions between the glycol and the water vapor in the gas are affected by
temperature. At higher temperatures, more water vapor will remain in the gas
stream. A cooler glycol temperature will decrease the glycol vaporization
losses but hydrocarbons may condense in the contactor.
Glycol Reboiler Heat Flux/Temperature:Glycol degradation
should be minimized by designing the glycol reboiler firetube with an average
heat flux of no higher than 10,000 BTU/hr/ft2. The normal range of heat flux is
6,000 - 10,000 BTU/hr/ftZ. Burner flame pattern and flame length should also be
designed to avoid hot spots on the firetube. Bulk temperature for triethylene
glycol should not exceed 400°F. The maximum tube wail temperature should
not exceed 430°F
Circulation Rates: Typical glycol type gas
dehydration units have glycol circulation rates from 2.0 to 3.0 gallons
of glycol per pound of water removed- Varies depends on Unit Spec & gas
quality.
Glycol Losses: For a properly designed gas
dehydration unit during normal operation, the glycol losses should not exceed 0.1 gallon of glycol per
million standard cubic feet of gas dehydrated.
GDU- CORROSION
CONTROL:
Variables affecting Corrosion Potential: Stream
compositions, operating pressure and temperature conditions, and design/fabrication
details such as metallurgy, stress, welding procedures and heat treatment all
have a part in the corrosion potential of a system. Since carbon steel is the
major material of construction for typical glycol-type gas dehydration units,
corrosive environments require special considerations.
Stream Compositions.
Of primary concern is the presence of acid gases (carbon dioxide- CO, and/or
hydrogen sulfide-H,S) and/or oxygen-02 in the flow streams.
Carbon dioxide partial
pressures in the gas phase below 3 psia typically do not require corrosion
control. Between 3 and 30 psia, some form of corrosion control may be required,
such as pH control or inhibitor injection.
Corrosion resistant
metals may also be needed. For carbon dioxide (CO,) partial pressures above 30 psia,
design/operational corrosion control measures will be required. Hydrogen
sulfide (H2S) and oxygen (O2) are corrosive at very low concentrations. In
addition to corrosion, hydrogen sulfide (H,S) can lead to sulfide stress
cracking (SSC)
INSTALLATION,
START-UP, OPERATION AND MAINTENANCE
Installation:
All equipment must be installed on an adequate foundation. The equipment should
be as level as possible for the most efficient operation. All items shipped
loose should be installed on the unit. This may include the stack, still
column, piping between the regenerator and contactor, and the vent line from the
still column. Normally the still column vapors are vented directly to the
atmosphere.
Vent piping
should be kept to a minimum. It should be remembered that these vapors contain
combustible hydrocarbons, corrosive components, and water which may condense
and freeze. Therefore, consideration must be given to the location assembled, all screwed and bolted connections
should be checked for tightness.
Start-up:
The unit should
be inspected before start-up to make certain that all valves are closed and all
regulators are backed off.
All relief
valves and critical shutdown devices should be operational. Admit supply gas to
the system and open isolation valves under all pressure gauges.
The contactor
should be purged with natural gas to eliminate air. It then should be brought
up to line pressure and checked for leaks.
Maintain the
contactor pressure, but do not flow gas at this point. The flash tanks and piping
should also be purged to eliminate air.
Open the cocks
on the glycol surge tank level gauge and the valve in the line between the
surge tank and the glycol/glycol heat exchanger.
Fill the
reboiler with glycol until the level comes about half way up in the surge tank
gauge. Allow approximately 25% of the surge tank for thermal expansion of the
glycol.
The glycol
circulation, including the return to the reboiler from the contactor, should be
fully established prior to ignition of the main burner.
Light the pilot
light and main burner as recommended. Heat the glycol until it reaches 390°F
and set the temperature controller. Continue heating the glycol until it
reaches 400°F and set the high temperature shutdown. These temperatures are typical:
however, some manufacturers and operators prefer somewhat different
temperatures.
Operating conditions
can also sometimes require different operating temperatures. It is highly
recommended that the glycol never be heated above 400°F because it starts decomposing
at 405°F.
The glycol level
in the surge tank should be brought to normal after circulation has been
established. All gauge cocks should be open and level controls set at this time.
Gas flow may now
be started through the contactor. The flow rate should be increased slowly to
prevent losing
liquid seals and
damage to the trays.
The unit is now
ready for final adjustments. This includes checking the reboiler temperature
setting, circulation rate, burner adjustment, valve function, level controller
function, and glycol level in the sure tank.
It is very
important to make sure that steam is coming out of the vapor outlet of the
still column. The circulation rate should be in accordance with the process
design specification.
Operation:
Routine
operation of gas dehydration units primarily involves periodic visits to
determine if everything is operating properly.
As a minimum,
the following items should be checked:
a. inlet gas
temperature and flow rate
b. contactor
pressure
c. reboiler
temperature
d. pump
operation
e. steam
from still column
f. level
of glycol in surge tank
g. burner
flame pattern and firetube appearance.
It is necessary
to periodically add glycol to the surge tank because a certain amount of glycol
loss is normal.
Other than that,
the units are designed for unattended operation as long as everything is functioning
properly.
If the unit is
designed for manual dumping of distillate from the reboiler and/or the glycol
flash separator, it will be necessary to check these levels during the periodic
visits.
There are
numerous operating problems that can be encountered with these units. Some of
the most common will be
discussed here.
Two factors
which greatly affect the ability of a unit to dehydrate gas are gas pressure
and temperature.
Small changes
from design in these variables can have a large effect on the water content of
the gas. Gas flow rate has a somewhat
smaller effect on equipment performance.
Cold outside air
temperatures can render a unit inoperable. It can freeze instruments and
controls, and can cause hydrates to form in scrubbers. If a unit is located in
an area where this is a problem, precautions should be taken. Examples are
heating coils in scrubbers, heating jackets on liquid discharge lines, cold
weather shrouds on glycol/glycol heat exchangers, and housing the entire
regenerator
Proper operation
of a unit depends on the cleanliness of the gas being processed. Many times, it
is necessary to install a coalescing filter separator immediately ahead of the
unit. This will remove compressor lube oil fog, small solids, distillate, salt,
etc. These impurities can plug equipment, coat packing, render the glycol less effective,
and coat the firetube which will cause it to burn out.
Plugging in the
still column or vent line can cause pressure to build up in the reboiler and
surge tank. This pressure should be checked periodically. Caution should be
used when opening connections: for example, to add glycol.
There are ways
of removing distillate once it gets into the regeneration system. The surge
tank may have a skimmer valve on it by which the distillate can be manually
drained. If the glycol flash separator is designed as a three phase
vessel, distillate may also be removed from the system at this point.
Maintenance:
It is necessary
to check the pH of the glycol periodically. It should be a neutral solution. Values
that vary from neutral can lessen the ability of the glycol to absorb water,
and may cause foaming or corrosion.
The elements in
all filters (coalescing, charcoal, sock, regulators, etc.) need to be checked
periodically and replaced as necessary.
Pumps require
routine maintenance and overhauling.
Dehydration
units may become plugged and packing may get a coating buildup. When this
happens, it is necessary that the system be thoroughly cleaned.
Nice Information!!
ReplyDeleteGet more details about Gas Dehydration - http://finepacindia.in/gas-dehydration.html
Nice blog great information...
ReplyDeleteThanks for sharing...
Flow Meter, Humidity Meter, Countroller, Temperature Controller
Informative Blog. Thanks for Sharing it. It gives information about Glycol Type Gas Dehydration Unit and its process.
ReplyDeleteThanks for sharing. Gas controller plays a crucial role in maintaining the delicate balance between energy supply and safety.
ReplyDeleteIt is a good article thanks for sharing this blog it gives lots of information.
ReplyDeleteACLS Certification
Love this post and the insight into your past.
ReplyDeleteACLS Certification Murrieta